IPS Test Type Description
Minimum
underfrequency
(81.S1)
The default underfrequency protection threshold is 49.8 Hz,
and the default protection time threshold is 0.1s.
Minimum
underfrequency
(81.S2)
The default underfrequency protection threshold is 47.5 Hz,
and the default protection time threshold is 0.1s.
Step 3 After the IPS test is complete, IPS State is displayed as IPS state success. Tap
Historical report in the upper right corner of the screen to view the IPS check
report.
----End
7.3 SmartLogger Networking Scenario
See the
Distributed PV Plants Connecting to Huawei Hosting Cloud Quick
Guide (Distributed Inverters + SmartLogger1000A + RS485 Networking)
and
PV Plants Connecting to Huawei Hosting Cloud Quick Guide (Inverters +
SmartLogger3000 + RS485 Networking)
. You can scan the QR code to obtain it.
Figure 7-18 SmartLogger1000A
Figure 7-19 SmartLogger3000
SUN2000-(3KTL-10KTL)-M1
User Manual 7 Man-Machine Interaction
Issue 02 (2020-11-20) Copyright © Huawei Technologies Co., Ltd. 82

Table of Contents

Other manuals for Huawei SUN2000-3KTL-10KTL-M1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-3KTL-10KTL-M1 and is the answer not in the manual?

Huawei SUN2000-3KTL-10KTL-M1 Specifications

General IconGeneral
BrandHuawei
ModelSUN2000-3KTL-10KTL-M1
CategoryController
LanguageEnglish

Related product manuals