8
Plug insert
To remove the AC connector, 
perform the operations in 
reverse order of installing the 
AC connector. Then, remove 
the plug insert, as shown in 
the following figure. 
Installing DC Input Power Cables
3.5
1. Ensure that the PV module output is well insulated to ground.
2. Use the Staubli MC4 positive and negative metal terminals and DC connectors supplied with 
the solar inverter. Using incompatible positive and negative metal terminals and DC connectors 
may result in serious consequences. The caused device damage is not covered under warranty.
3. The DC input voltage of the solar inverter must not exceed maximum input voltage.
4. Before installing DC input power cables, label the cable polarities to ensure correct cable 
connections.
5. If DC input power cables are reversely connected, do not operate the DC switch as well as 
positive and negative connectors immediately. Failing to do so may cause device damage, 
which is not covered under warranty. Wait until the solar irradiance declines at night and the 
PV string current reduces to below 0.5 A, and then turn off the DC switch and remove the 
positive and negative connectors. Correct the string polarity before reconnecting the PV string 
to the solar inverter.
1. Assemble DC connectors.
Click
Positive metal terminal
Negative metal terminal
Ensure that the cable cannot 
be pulled out after being 
crimped.
Positive connector
Negative 
connector
Use the wrench shown 
in the figure to tighten 
the locking nut. When 
the wrench slips during 
the tightening, the 
locking nut has been 
tightened.
Ensure that cable 
polarities are correct.
PV-CZM-22100/19100
PV-MS-HZ
Open-end wrench
If the PV strings are configured with Smart PV Optimizers, refer to the 
Smart PV Optimizer 
Quick Guide 
to check the cable polarity.