A Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
5%–95% RH (non-condensing)
0–4000 m
When the altitude ranges from 2000 m to 4000 m, the
operating temperature decreases by 1°C for each additional
200 m.
There should be no conductive dust, corrosive gas, or
explosion hazard.
Dust, corrosive substances, pests, molds, and other
indicators should be controlled in accordance with Class
3.1 requirements in ETSI EN 300 019-1-3 (V2.3.2 or
later).
TPD48202B-N20B1: ≤ 2000 A (load output: 2000 A;
battery charge current: 400 A)
TPD48302B-N20B1: ≤ 3000 A (load output: 3000 A;
battery charge current: 500 A)
Regulated voltage
precision
≤ 500 mV (ambient temperature: 20°C)
2000 mm x 800 mm x 600 mm
On a concrete floor or ESD floor
Routed in and out from the top or bottom
Maintained from the front or rear (at least 650 mm away
from a wall)