Item 15 kVA 20 kVA
Input voltage 80–280 V AC, single-phase
(When the voltage is 80–
176 V AC, the load power
is linearly derated to
40%–100%.)
138–485 V AC, three-
phase (When the voltage
is 138–305 V AC, the load
power is linearly derated
to 40%–100%.)
80–280 V AC, single-
phase (When the voltage
is 80–176 V AC, the load
power is linearly derated
to 40%–100%.)
138–485 V AC, three-
phase (When the voltage
is 138–305 V AC, the load
power is linearly derated
to 40%–100%.)
Input power
factor (100%
resistive load)
> 0.99
No-load loss < 200 W
Double-power
input
Enabled
Startup voltage 120–280 V AC
Diesel generator
input capacity
Minimum 1.5 times the UPS rated capacity
9.4 Bypass Input Electrical Specications
Table 9-6 Bypass input electrical specications
Item
6 kVA 10 kVA 15 kVA 20 kVA
Bypass voltage Upper threshold: 10%, 15%, 20%, 25%, 30%@208 V AC
Upper threshold: 10%, 15%, 20%, 25%@220 V AC
Upper threshold: 10%, 15%, 20%@230 V AC
Upper threshold: 10%, 15%@240 V AC
Lower threshold: 10%, 20%, 30%, 40%, 50%, 60%
Bypass frequency
tolerance
Maximum ±6 Hz (congurable on the LCD)
Bypass overload
capability
Load < 125%: continuous in bypass mode
125% ≤ load < 150%: 1 minute in bypass mode
Load ≥ 150%: 100 milliseconds in bypass mode
The input switch may trip in advance.
Input mode One power source One power source
Two power sources
UPS2000-G- (6 kVA-20 kVA)
User Manual 9 Technical Specications
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 116