No. Item Description
3 UPS subcategory G: series name
4 Output capacity 6K: 6 kVA
10K: 10 kVA
15K: 15 kVA
20K: 20 kVA
5 UPS type RT: rack- and tower-mounted unit
RR: rack-mounted unit
TT: tower-mounted unit
TM: modular tower-mounted unit
RM: modular rack-mounted unit
6 Built-in battery
(optional)
S: standard model, which provides only a
standard battery pack.
L: long backup time model. You need to use an
external large-capacity battery pack.
7 Model identier 01
2.2 Working Principle
2.2.1 Conceptual Diagram
Figure 2-2 shows the UPS conceptual diagram.
Figure 2-2 Conceptual diagram
2.2.2 Working Modes
The UPS has the following working modes:
Normal mode
When the mains is normal, the rectier boosts the mains input voltage and
converts the AC power into stable DC power for the inverter, and the mains
charges batteries over a charger. Then the inverter converts the DC power into
stable AC power, which is supplied to loads.