9.5 Output Electrical
Specications
Table 9-7 Output Electrical Specications
Item 6 kVA 10 kVA 15 kVA 20 kVA
Rated capacity 6 kVA 10 kVA 15 kVA 20 kVA
Output power
factor (PF)
0.9
Rated output
voltage
208 V AC, 220 V AC, 230 V
AC, or 240 V AC (single-
phase output; select a
voltage system by setting a
voltage level on the LCD.)
208 V AC, 220 V AC, 230
V AC, or 240 V AC (single-
phase output; select a
voltage system by setting
a voltage level on the
LCD.)
380 V AC, 400 V AC, or
415 V AC (three-phase
output; select a voltage
system by setting a
voltage level on the LCD.)
Output voltage
tolerance
±1%
Total harmonic
distortion of
output voltage
(THDv)
< 4% (non-linear load)
< 2% (resistive load)
Crest factor A maximum of 3:1
Inverter overload
capability
105% ≤ load < 125%: transfer to bypass mode after 5
minutes
125% ≤ load < 150%: transfer to bypass mode after 1
minute
Load ≥ 150%: transfer to bypass mode after 100
milliseconds
The UPS stops supplying power if the bypass is
abnormal.
Dynamic voltage
tolerance
±5%
Output voltage
unbalance
- ±1% (balanced load)
±3% (unbalanced load)