Parallel-System Load Screen
Figure 4-15 Parallel-System Load screen
Table 4-11 Parallel-System Load
Item Description
N+X Parallel-System A parallel system is running. X (value range: 0–3)
indicates the number of redundant UPSs
(congurable on the LCD); N (value range: 1–4)
indicates the number of requisite UPSs (total
number of UPSs minus X). The total number of
UPSs is automatically
identied by the system.
Sys. Sout_A/Sys. Sout_ B/
Sys. Sout_C
System phase A, B, and C apparent power
displayed on the Parallel-System Load screen.
The parameter is Sys. Sout in the case of single-
phase input; the parameters are not displayed in
single UPS mode.
Sys. Pout_A/Sys. Pout_ B/
Sys. Pout_C
System phase A, B, and C active power displayed
on the Parallel-System Load screen. The
parameter is Sys. Pout in the case of single-phase
input; the parameters are not displayed in single
UPS mode.
Sys. Load ratio_A/Sys.
Load ratio_B/Sys. Load
ratio_C
System phase A, B, and C load ratio displayed on
the Parallel-System Load screen. The parameter
is Sys. Load ratio in the case of single-phase
input, and the parameters are not displayed in
single UPS mode.
NO TE
System information is not displayed in single UPS mode.
UPS2000-G- (6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 53