Item Description Default Value Value Range
Overcurre
nt thres.
Set an alarm threshold for
battery overcurrent. The
parameter is congurable in
any mode.
Note: The overcurrent alarm
threshold can be set only
for the UPS2000-G-15
kVA/20 kVA.
Standard
model: 3.0 A
Long backup
time model:
6.0 A
Standard
model: 2.0–4.0
A
Long backup
time model:
4.0–8.0 A
Equalized Charge screen
Figure 4-37 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Table 4-27 Equalized Charge screen (UPS2000-G-15KRTL-01/UPS2000-
G-20KRTL-01)
Item
Description Default
Value
Value Range
Equalized
charging
Determine whether to enable
equalized charging. The
parameter is congurable in
any mode.
Enabled Disabled,
Enabled
Time
interval
Set the time interval for
equalized charging. The
parameter is congurable in
any mode.
60 days 30–180 days
Voltage Set the battery equalized
voltage. The parameter is
congurable in any mode.
2.35 V/cell 2.33–2.40 V/cell
Max. time Set the maximum equalized
charge time. The parameter
is congurable in any mode.
960 min 600–999 min
Figure 4-38 Equalized Charge screen (UPS2000-G-6KRTS/UPS2000-
G-10KRTS/UPS2000-G-15KRTL/UPS2000-G-20KRTL)
UPS2000-G- (6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 73