EasyManua.ls Logo

Huawei UPS5000-A-30 kVA - Page 17

Huawei UPS5000-A-30 kVA
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 1-2 Power cable terminal requirements
Model Port Connection Method Bolt
Specicat
ions
Bolt Hole
Diameter
Torque
30–40 kVA Mains
input
Crimped OT terminal M6 6.5 mm 4.5 N·m
60–80 kVA Crimped DT terminal M8 9 mm 13 N·m
120 kVA Crimped DT terminal M10 11 mm 27 N·m
30–40 kVA Bypass
input
Crimped OT terminal M6 6.5 mm 4.5 N·m
60–80 kVA Crimped DT terminal M8 9 mm 13 N·m
120 kVA Crimped DT terminal M10 11 mm 27 N·m
30–40 kVA Battery
input
Crimped OT terminal M8 9 mm 13 N·m
60–80 kVA Crimped DT terminal M10 11 mm 27 N·m
120 kVA Crimped DT terminal M12 13 mm 47 N·m
30–40 kVA Output Crimped OT terminal M6 6.5 mm 4.5 N·m
60–80 kVA Crimped DT terminal M8 9 mm 13 N·m
120 kVA Crimped DT terminal M10 11 mm 27 N·m
30–40 kVA PE Crimped OT terminal M6 6.5 mm 4.5 N·m
60–120
kVA
Crimped DT terminal M8 9 mm 13 N·m
Figure 1-2 OT terminal
UPS5000-A-(30 kVA–120 kVA)
Quick Guide 1 Installation
Issue 14 (2022-09-06) Copyright © Huawei Digital Power Technologies Co., Ltd. 10

Other manuals for Huawei UPS5000-A-30 kVA

Related product manuals