1.3.5 Connecting a Remote EPO Switch
NO TICE
The product is not provided with an EPO switch or cable. Prepare them by
yourself before installation. The recommended cable is 22 AWG.
Equip the EPO switch with a protective cover to prevent misoperations, and
cover the cable with protective tubing.
Triggering EPO will shut down the
rectier, inverter, charger, and static bypass,
but does not disconnect the UPS mains input. To power o the UPS completely,
you can turn
o the upstream input switch when you trigger EPO.
Connect the EPO switch to the specied dry contact on the UPS using a cable.
NO TE
By default, the EPO switch is o. When it is turned on, EPO is triggered.
Figure 1-66 Cable connection for an NO EPO switch
1.4 Installing a Parallel System
Procedure
Step 1 Ground each UPS in a parallel system separately, and connect power cables and
battery cables.
Step 2 Select a parallel mode and connect cables to the parallel system based on site
requirements.
UPS5000-A-(30 kVA–120 kVA)
Quick Guide 1 Installation
Issue 14 (2022-09-06) Copyright © Huawei Digital Power Technologies Co., Ltd. 51