2.3 Clearing the EPO State
Procedure
Step 1 Turn
o the EPO switch.
Step 2 Clear the EPO alarm.
LCD
On the main menu screen, choose Alarms > Clear Faults. In the displayed
dialog box, press
to clear the EPO alarm.
WebUI
On the WebUI, choose Monitoring > UPS System > Running Control and
click Clear Fault. The EPO alarm is cleared.
On the old WebUI, choose Monitoring > Control and click Clear Fault to
clear the EPO alarm.
Step 3 View active alarms and ensure that the EPO alarm is cleared. If the input of the
system bypass is normal, the UPS switches to the bypass mode.
LCD
On the main menu screen, choose Alarms > Active Alarms to check that the
EPO alarm has been cleared.
WebUI
On the WebUI, choose Home > Active Alarm to check that the EPO alarm
has been cleared.
On the old WebUI, choose Monitoring > Active Alarms to check that the
EPO alarm has been cleared.
Step 4 Start the inverter.
----End
UPS5000-A-(30 kVA–120 kVA)
Quick Guide 2 Single UPS Commissioning
Issue 14 (2022-09-06) Copyright © Huawei Digital Power Technologies Co., Ltd. 66