No. Item Acceptance Criteria
13 Operating environment The inside and outside of the cabinet are
free from conductive dust or other
sundries.
30 kVA/40 kVA UPS
There is no foreign matter (such as
copper wires and screws) between
wiring terminals. Cables are
crimped according to standards,
and there is no bare copper wire.
There is no foreign matter in the
wiring terminal box.
60 kVA/80 kVA/120 kVA UPS
There is no foreign matter
between wiring terminals. Cables
are crimped according to
standards, and there is no bare
copper wire.
There is no foreign matter at the
bottom of the UPS.
14 DIP switch settings Toggle switch 4 is set to ON.
15 Short circuit between
copper bars
Check that copper bars are open-
circuited using a multimeter.
NO TE
After installing cables and verifying the installation, use sealing putty to seal the gaps
between the cables and the cabinet.
After verifying the installation, reinstall all the covers.