24
Trouble Shooting Continued
Condition Troubleshooting
Case is not Holding
Temperature
(Continued)
Check Merchandising Planogram / Observe Load Limits
-Evenly distribute product as much as possible
-Avoid uneven stacking
-Orient product on round ends or corner in a radial pattern in relation to the
discharge air walls
-Create a channel or path for discharge air to travel towards products at the edge of
the merchandiser
-Set product back from shelf or deck product stop by up to 1" to allow discharge air
to surround the product
-Merchandise product as flat as possible to keep it in contact with a shelf or deck
pan surface
-Move products with lower moisture content closer to the Center Discharge Column
Case Lights are not
working
Check that Light switch is in the ON position
Check for burned out bulbs. Turn lights off & replace.
Clean dirt and dust from the bulbs to prevent flickering.
Check to ensure voltage at LED Driver. If voltage is entering but not exiting the LED
Driver, LED Driver is faulty.
Check that ALL lights are plugged in and receptacles capped.
Control Display is
Flashing
Check Temperature Controller section in this manual.
Condensing Unit is not
Operating (Self-
Contained
units only)
Check Temperature Controller section in this manual.
Check that the power is turned on.
Review Temperature Controller's Settings for accuracy
The condensing unit may be equipped with its own controller and display. This controller
is only for the condensing unit and does not control the temperature of the case. Do not
adjust settings on this controller. Only a qualified service technician should attempt to
change settings on this controller
The Danfoss controller located on the switch panel (see page 16) is for case temperature
control. Note that when the Danfoss controller is not calling for cooling, the display on the
condensing unit controller will go off. This is considered normal operation.