EasyManua.ls Logo

HydroTherm KN-2 - Zoning with Zone Valves

HydroTherm KN-2
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P/N 42-9450 8/08 Copyright 2008 Hydrotherm
Page 13 KN INSTALLATION AND OPERATION INSTRUCTIONS
Water piping (continued)
Figure 8 Suggested piping — single boiler — zone valve zoning — two-pipe or series loop (left), or primary/secondary piping (right)
LEGEND • • • • • • •
1 KN boiler
2 Boiler circulator
3 System circulator
4 Boiler/system circulator
5 Indirect- red DHW tank
(when used)
6 DHW circulator
7 Flow/check valve
8 Cold water  ll line
9 Expansion tank (shown with diaphragm-type — see
page 12 for piping a closed-type tank)
Expansion tank (shown with diaphragm-type — see
page 12 for piping a closed-type tank)
10 Air separator with automatic air vent (Replace air vent
with piping to the tank  ing on closed-type expansion
systems.)
11 Low water cut-o (when required)
12 Extra high limit (when required)
13 Zone valve
14 Zone circulator
15 Di erential pressure by-pass valve — Use when high-
head circulator may cause noise, erosion or valve li ing
problems when only a few zone valves are open.
16 Boiler postpurge circulator (see page 11) KN
-
2 only
17 Header sensor, required where shown
Isolation valve
Purge valve — Suggested locations allow for improved
system  lling and draining and initial air elimination.
Temperature gauge
Zoning with zone valves
Flow balancing and control
On large systems, or when using a high-head circulator, install a di erential
pressure by-pass valve to limit the head applied to the zone valves.
Some systems may require balancing valves to control  ow in the loops.
DHW operation, when required
e piping shown throughout this manual allows for domestic water
heating without  ow through the heating loop(s).  is is important for
summertime operation of DHW tanks.
Make sure to incorporate  ow/check valves as shown.  ese prevent forced
ow in idle zones.
5
*
**

Other manuals for HydroTherm KN-2

Related product manuals