HMS-600W / 800W USER MANUAL 20
need to deal with it.
2. In case of frequent occurrence but automatic recovery, please
confirm if the grid voltage is outside the permissible range due to
local grid conditions, try to modify the values of the monitored
operational limits after informing the electric utility company first.
⒊If it cannot be recovered for a long time, please confirm:
①whether the AC circuit breaker is disconnected
②whether the AC terminal is in good connection
③whether the power supply line is normal
④ whether the safety regulation settings are normal
13
EEPROM Error, e.g.
transition
disturbance
Micro CPU read EEPROM
failed
Disconnect the inverter from the utility grid and the PV array, and
reconnect it after LED turns off. If this fault is still being displayed,
please contact the service.
14
Internal
communication
fault
Master CPU communicate
with slave CPU abnormal
Disconnect the inverter from the utility grid and the PV array, and
reconnect it after LED turns off. If this fault is still being displayed,
please contact the service.