11 HMS-600W / 800W USER MANUAL
5.2 Mounting
5.2.1 Micro Inverter Installation
1. Mark the position of each Micro Inverter on the rail, according to the PV module
layout.
2. Fix the screw on the rail.
3. Mount Micro Inverter at each of these locations and tighten the screws.
5.2.2 AC Connection
1. Insert the AC extension cable into the AC connectors of the two inverters
until it clicks.
2. Connect the AC end cable to the distribution box, and wire it to the local
grid network.
3. Please plug the AC end Cap to make last connection water and dust-proof.
End Cap’s ingress protection is IP65 and cannot be soaked in water.
4. Push the buckle open with the tool as shown, rotate the latch as shown,
unplug the male and female ends to unlock the cables.
Check all the wires of the installation before connecting to the grid to
be sure they match. Wrong cable polarity can damage the Micro
Inverters, such an issue is not covered by the warranty.