Operational settings in the Advanced Setup Menu
Mode Setting Description
Temp.
Range
Default
DHW Boiler Pump See Boiler Pump on page 87. On-Off On
Boiler
Supply°
Target temperature for the outlet 95 °F-185 °F 170 °F
Maximum
Supply°
Limit to prevent overheating of supply
water
41 °F-190 °F 190 °F
Supply diff. Boiler will shut off when the supply water
temperature is half the differential setting
below the boiler target temperature and fire
when the supply water temperature is half
the differential setting above the boiler
target
3 °F-62 °F 20 °F
Tank
Setpoint°
Target temperature of DHW 95 °F-160 °F 140 °F
Tank diff. 3 °F-62 °F 10 °F
Ramp
Speed
See Ramp Speed on page 91. 1-10 7
Priority Priority of the DHW load against other
loads
20-90 87
Pump Post
Purge
See Pump Post Purge (sec) on page 90. 0-900
seconds
180 secs
Water°
From
See Water° From on page 92. Outlet, Sec.
Loop, DHW
Outlet
Tank° From Sec. Loop,
DHW
DHW
Section: Operating concepts