Operational settings in the Setup Menu
Mode Setting Description
Temp.
Range
Default
Min.
Contro
(2.1VDC)
Lowest temperature per minimum voltage
sent to the controller
32 °F-185 °F 100 °F
Maximum
supply
Maximum limit to prevent overheating 41 °F-190 °F 180 °F
Failsafe
enable
(if no signal boiler comes on - prevent no
heat occurring and ext. controller failure
Enabled or
Disabled
Disabled
Failsafe
setpoint
86 °F-185 °F 86 °F
Priority Priority of the call for heat by external
control against other loads
Very Low -
Very High
High
Pump Post
Purge
Time (seconds) the pump will operate after
satisfying call for heat from external control
0-900
seconds
300 secs
Table 4 Temperature ranges and defaults in declared loads - Setup
2.10 Operational settings in the Advanced Setup menu:
temperature ranges and defaults
Operational settings in the Advanced Setup Menu
Mode Setting Description
Temp.
Range
Default
Reset
Heating
Current
Targe
95 °F-185 °F 130 °F
Emitter Type of heating device used to transfer
heat in a building (radiant, air handler, cast
radiator, baseboard)
Boiler Pump See Boiler Pump on page 87. On-Off On
Design
Supply°
Desired boiler outlet temperature on the
coldest day
50 °F-190 °F 125 °F
Design
Outdoor°
Coldest expected outdoor temperature
typically experienced at the installation
site. Set the Design Outdoor Air
temperature correctly for the geographic
location; consult a local IBC wholesaler or
the heat loss calculation documentation
used in the design of the heating system.
-76 °F-86 °F 14 °F