Operational settings in the Advanced Setup Menu
Mode Setting Description
Temp.
Range
Default
Summer
Shutdown°
Cut-off level for outdoor temperature that
stops further heating
32 °F-122 °F 65 °F
Maximum
Supply°
Highest supply water temperature 70 °F-147 °F 70 °F
Minimum
Supply°
Lowest supply water temperature 70 °F-147 °F 70 °F
Supply Diff'l Boiler will shut off at half differential setting
when supply water temperature is half the
differential setting below the boiler Current
Target° and fire when the supply water
temperature is half half the differential
setting above the boiler Current Target°
3 °F-62 °F 20 °F
Ramp
Speed
See Ramp Speed on page 91. 1-10 3
Priority See Priority on page 90. 20-90 28
Pump
Purge
See Pump Post Purge (sec) on page 90. 0-900
seconds
0
Indoor
From°
See Indoor ° From on page 89. Indoor / Sec.
Loop
Indoor
Outdoor
From°
See Outdoor ° From on page 90. Outdoor,
Sec. Loop,
DHW
Outdoor
Water
From°
See Water° From on page 92. Outlet, Sec.
Loop, DHW
Burner On
From
Type of control used to control boiler
supply of heat.
Thermostat
or Ext.
Control
Thermostat
Advanced
Reset
Current
Target°
95 °F-185 °F 130 °F
(When
Advanced
Reset
check box
is
checked)
Emitter Type of heating device used to transfer
heat in a building (radiant, air handler, cast
radiator, baseboard)
Boiler Pump See Boiler Pump on page 87. On-Off On
Design
Supply°
Desired boiler outlet temperature on the
coldest day
50 °F-190 °F 125 °F
2.10 Operational settings in the Advanced Setup menu: temperature ranges and defaults