Chapter 1. General description 5
1.2 Operating environment
Table 1-1 lists the operating environment specifications for the servers.
Table 1-1 Operating environment for Power 750 Express and Power 760
Description Operating Non-operating
Temperature 5 - 35 degrees C
(41 - 95 degrees F)
5 - 45 degrees C
(41 - 113 degrees F)
Relative humidity 20 - 80% 8 - 80%
Maximum dew point 29 degrees C
(84 degrees F)
28 degrees C
(82 degrees F)
Operating voltage 200 - 240 V AC Not applicable
Operating frequency 50 - 60 ± 3 Hz Not applicable
Power consumption Power 750:
2400 watts maximum (system unit
with 32 cores installed)
Power 760:
2400 watts maximum (system unit
with 48 cores active)
Not applicable
Power source loading Power 750:
2.45 kVA maximum (system unit
with 32 cores installed)
Power 760:
2.45 kVA maximum (system unit
with 48 cores active)
Not applicable
Thermal output Power 750:
8,189 BTU/hr maximum (system
unit with 32 cores installed)
Power 760:
8,189 BTU/hr maximum (system
unit with 48 cores active)
Not applicable
Maximum altitude 3048 m
(10,000 ft)
Not applicable
Noise level for system unit Power 750 (system unit with 32 installed cores):
7.1 bels (operating or idle)
6.6 bels (operating or idle) with acoustic rack doors
Power 760 (system unit with 48 active cores):
7.1 bels (operating or idle)
6.6 bels (operating or idle) with acoustic rack doors