EasyManuals Logo

ICM Controls SC2311L User Manual

ICM Controls SC2311L
2 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
ONE-YEAR LIMITED WARRANTY
TheSellerwarrantsitsproductsagainstdefectsinmaterialorworkmanshipforaperiodofone(1)yearfromthe
dateofmanufacture.TheliabilityoftheSellerislimited,atitsoption,torepair,replaceorissueanon-casecreditfor
thepurchasepricesofthegoodswhichareprovidedtobedefective.Thewarrantyandremediessetforthherein
donotapplytoanygoodsorpartsthereofwhichhavebeensubjectedtomisuseincludinganyuseorapplication
inviolationoftheSeller’sinstructions,neglect,tampering,improperstorage,incorrectinstallationorservicingnot
performedbytheSeller.InordertopermittheSellertoproperlyadministerthewarranty,theBuyershall:1)Notify
theSellerpromptlyofanyclaim,submittingdatecodeinformationoranyotherpertinentdataasrequestedbythe
Seller.2)PermittheSellertoinspectandtesttheproductclaimedtobedefective.Itemsclaimedtobedefective
andaredeterminedbySellertobenon-defectivearesubjecttoa$30.00perhourinspectionfee.Thiswarranty
constitutestheSeller’ssoleliabilityhereunderandisinlieuofanyotherwarrantyexpressed,impliedorstatutory.
Unlessotherwisestatedinwriting,Sellermakesnowarrantythatthegoodsdepictedordescribedhereinaretfor
anyparticularpurpose.
LIAF022
Patent No. - Design: 424,953
Patent No. - Thermal Intrusion Barrier: 6,597,275
Patent Pending - SimpleSet
TM
Target Programming Technology
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276
www.icmcontrols.com
Operating Modes
ThesearethepossibleoperatingmodesoftheSC2311L.
Off Mode
Inoffmode,thethermostatwillnotturnontheheatingorcoolingappliances.
Note 2: The indoor fan can be activated in every mode by sliding the Auto/On fan to the On
position.
Note 2: Off mode in used to enter the conguration setup (by pressing LEFT and RIGHT
simultaneously for 5 seconds).
Cool Mode
Incoolmode,thethermostatcontrolsthecoolingsystem.
Thereisafourminutetimedelayafterthecompressorturnsoff.Thisprotectsthecompressor.
Heat Mode
Inheatmode,thethermostatcontrolstheheatingsystem.
Forheatpumps,thereisafourminutetimedelayafterthecompressorturnsoff.Thisprotectsthe
compressor.
Emergency Heat Mode(Heatpumpsystemsonly)
Inemergencyheatmode,theheatpumpsystemwillbedisabledandauxiliaryheatwillbecomethe
primarysourceofheat.
ENTER Emergencyheatmodebypressingtheupbuttonfortensecondswhileinheatmode.“EH”
willthendisplayonthescreen.
EXIT Emergencyheatmodebypressingtheupbuttonfortenseconds.“EH”willnotdisplayon
thescreenwhenyouexitemergencyheatmode.
TheSC2311LalsoexitsemergencyheatmodewhenthemodeswitchismovedtoCool.
Thisfeatureisusedfortransferringthecongurationsettingsfromthemastertothetarget
thermostat.Allthermostatsforajobcanbemountedandpoweredup.Congureonethermostat.This
willbethemaster.Themasterwillbeusedtocopythecongurationtotherestofthethermostats.
Preparing the master to Send:
1.Themastermustbepoweredby24VAC.
2.VerifythemasterthermostatisinOFFmode.Slidesystemswitchtocenter
position.
3.Removecoverofthemasterthermostatbygentlypullingnearoneofthecorners
atthetopofthethermostat.
4.PresstheupanddownbuttonsandLEFTswitchsimultaneouslyfor5seconds.
5.TheOUTscreendisplaysindicatingthemasterthermostatisreadyto
transferdata.
Note: Press the up and down buttons and LEFT switch simultaneously for 5
seconds to exit from data transfer mode and to return the master to the
OFF mode.
6.Connectthemastertothetargetusingthe3wireconnector.Attachoneendto
theMaster’sFPpinsandtheotherendtotheTarget’sFPpins.
Note: Target thermostat must be powered by 24 VAC for eld programming
to occur.
Whentheconnectionhasbeenmadecorrectly,themasterthermostatwillpower
upandthetargetwillcountfrom6downto1.ItwillthendisplayLOCconrming
thedatahasbeensavedinmemory.
Whenalltargetthermostatshavebeencompleted,reinstallthemasterthermostat.
PresstheupanddownbuttonsandtheLEFTswitchsimultaneouslyfor5secondstoexit
fromthedatatransfermodeandtoreturnthemasterthermostattotheOFFmode.
SimpleSet
TM
Field Programming
FPPins
SC2010 N/L
Lockout Feature
TheSC2311Lhasabuttonlockoutfeaturesothetemperatureadjustmentisprohibited
orlimited.SelecttheappropriatelockoutfromCongurationModeSettings(Step7)of
thisguide.
ToactivatetheLOCfeature:
1.SimultaneouslypresstheLEFT, RIGHT andUPbuttonsfor10seconds.
2.LOCwilldisplayandthelockoutfunctionwillbeenabled.
TodeactivatetheLOCfeature,repeatsteps1and2above.
Troubleshooting
Symptom Remedy
Nodisplay Checkfor24VACatthermostat;displayisblankwhen24VACisnot
present
Systemfandoesnotcomeon
properly
Verifywiringiscorrect,checkheatsourcecongurationsettings
(seeCongurationModeSetting5)
Allthermostatbuttonsare
inoperative
Verify24VACispresent;unitlocksoutwhen24VACisnotpresent
Noresponsewithrstbuttonpress Firstbuttonpressactivatesbacklightonly
Thermostatturnsonandofftoo
frequently
Adjusttemperaturedifferential(seeCongurationModeSetting2)
Fanrunscontinuously SlideFANswitchtoautototurnfanoff
Roomtemperatureisnotcorrect Calibratethermostat(seeCongurationModeSetting10)
LOCdisplayswhenanybuttonis
pressed
Thermostathasthebuttonlockoutfunctionactivated
(seeLockoutFeature,andCongurationModeSetting7)
HeatorCoolnotcomingon Verifywiringiscorrect,verifycongurationsettingsarecorrect
Problemnotlistedabove PressResetbuttononce*
* Reset Button Function:Congurationsettingsareunchangedanddisplayisrefreshed.
Starting the Thermostat
RoomTemperature
CAUTION!
: Do not use air conditioning when the outdoor temperature is below 50 degrees.
This can damage your air conditioning system and cause personal injuries.
1.MovetheFan Auto/OnswitchtotheAutoposition.
2.MovetheCool/Off/HeatswitchtoCoolorHeat,dependingontheseason.
Mode of Operation
TheSC2311Lisatwo-stageheat,one-stagecoolthermostat.Itfunctionswithairconditioning,heat
pumps,gas,oilorelectricheat.
Thethermostatactivatestherststageheatwhentheroomtemperatureisbelowtheheatset
temperature(bythedifferentialtemperature).Secondstageheatwillbeactivatediftheroom
temperaturecontinuestodrop.Theheatoutputsarestagedoffastheroomtemperatureincreases.
Forheatpumpsystems,thethermostatwillnotletthecompressorcomeonforfourminutesafterit
turnsoff.Thisprotectsyourcompressor.
Whentheroomtemperatureisgreaterthanthecoolsettemperature(bythedifferentialtemperature),
thecoolingdeviceisactivated.Thecooloutputisturnedoffastheroomtemperaturedrops.The
thermostatwillnotletthecompressorcomeonforfourminutesafteritturnsoff.Thisprotectsyour
compressor.
TheSC2311Lhasthefollowingoperatingmodes:OFF,Heat,EmergencyHeat,andCool.InOFF
mode,thethermostatwillnotturnonheatingorcoolingdevices.IntheHeatmode,thethermostat
controlstheheatingsystem.Forheatpumpsystems,EmergencyHeatmodeisusedtobypass
thecompressor(onlybackupheatoperates).IntheCoolmode,thethermostatcontrolsthecooling
system.TheindoorfancanbeturnedoninalloperatingmodesusingtheFanswitch.
Fan Test
1. SlideFanswitchtoOnposition.
2. Indoorfanturnson.
Auto
On
Auto
On
3. SlideFanswitchtoAutoposition.
4. Indoorfanturnsoff.
Oncethethermostatisinstalled,itshouldbethoroughlytested.
CAUTION!:
Do not energize the air conditioning system when the outdoor temperature is
below 50 degrees. It can result in equipment damage or personal injury.
Testing the Thermostat
Cool Test
1. SlideModeswitchtoCoolmode.
2. Adjustsettemperaturesoitis5degreesbelowroomtemperature.
3. Airconditioningshouldcomeonwithinafewseconds.
4. Adjustthesettemperature2degreesabovetheroomtemperatureandtheA/Cshouldturnoff.
Theremaybeafandelayonyoursystem.
Note: There is a four minute time delay to protect the compressor after it turns off. To
temporarily bypass the four minute delay, slide the Mode switch to OFF for 2 seconds
and then back to Cool.
CoolOffHeat
Heat Test
1. SlideModeswitchtoHeatmode.
2. Adjustthesettemperaturesoitis5degreesabovetheroom
temperature.
3. Heatshouldcomeonwithinafewseconds.
4. Adjustthesettemperaturesoitis2degreesbelowtheroom
temperatureandtheheatshouldturnoff.Theremaybeafandelayonyoursystem.
Note: There is a four minute time delay to protect the compressor after it turns off. To
temporarily bypass the four minute delay, slide the Mode switch to OFF for 2 seconds
and then back to Heat.
CoolOffHeat

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ICM Controls SC2311L and is the answer not in the manual?

ICM Controls SC2311L Specifications

General IconGeneral
BrandICM Controls
ModelSC2311L
CategoryThermostat
LanguageEnglish

Related product manuals