EasyManua.ls Logo

ICON DPC1 - Page 6

ICON DPC1
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BIA-DPC1 rev 4 Page 6
The following chart shows main technical parameters for the Controller DPC1
Main technical characteristic
Control characteristic
Double liquid level control
pressure control
Control method
Manual/Auto
Liquid level control characteristic
pulse electrode probe and float switch
Pressure control characteristic
pressure switch and pressure tank
Main technical data
Rated output power
0.37 2.2 kW (0.5 3.0 hp)
Rated input voltage
240V
Trip response time of overload
5 sec - 5 min
Trip response time of open phase
< 2 sec
Trip response time of short circuit
< 0.1 sec
Trip response time of under/over voltage
< 5 sec
Trip response time of dry run
6 sec
Recovery time of over load
30 min
Recovery time of under/over voltage
5 min
Recovery time of dry run
30 min
Trip voltage of over voltage
115% of rated input voltage
Trip voltage of under voltage
80% of rated input voltage
Liquid level transfer distance maximum
1000m
Protection functions
Dry run
Over load
Transient voltage
Under voltage
Over voltage
Pump stalled
Short circuit
Main installation data
Working temperature
-25 to +55 deg C
Working humidity
20% to 90% Relative Humidity, non-condensing
Degree of protection
IP54
Install position
Vertical
Unit dimensions (L x W x H)
30.2 x 24.0 x 12.0 cm
RS485 technical data
Physical interface
RS485 Bus Interface: asynchronous semi duplex
Baud rate
1200,2400,4800,9600 bps (default 9600bps)
Protocol type
MODBUS protocol (RTU)

Table of Contents