ICP 9MPT - Exhaust Blower and Condensate Drain Trap; Exhaust Blower Assembly; Condensate Drain Trap Installation

ICP 9MPT
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Two- Stage Multi Position Furnace
Service
Manual
15
440 08 2002 02
“A”
“A”
Inlet
Figure 19
Sidewall Inlet Vent and Exhaust--
Air Termination
Dimension A” is touching or 2² maximum separation.
12²
²²
² Min. Grade
or Snow Level
18²
²²
² Min. for
Cold Climates
(Sustained Below 0°
°°
° F)
8²
²²
² Min.
20¢
¢¢
¢ Max.
8²
²²
² Min.
Exhaust
Exhaust
8²
²²
² Min.
8²
²²
² Min.
20¢
¢¢
¢ Max.
Figure 20
Sidewall Inlet Vent and Exhaust--Air
Termination with Exterior Risers
Dimension A” is touching or 2² maximum separation.
12²
²²
² Min.
Grade or
Snow Level
18²
²²
² Min. for Cold Climates
(Sustained Below 0°
°°
° F)
Inlet
“A”
“A”
12²
²²
² Min.
Grade or
Snow Level
Exhaust
8²
²²
² Min.
20¢
¢¢
¢ Max.
Figure 21
Rooftop Inlet Vent and Exhaust--
Air Termination
25--22--43
18²
²²
² Min. for Cold Climates
(Sustained Below 0°
°°
° F)
Inlet
OVERHANG
12²
²²
² MIN.
12²
²²
² MIN. Ground Level
OR Snow Level
INLET
EXHAUST
90°
°°
°
25-- 23--73
Figure 22
Recommended Alternate Installa-
tion for Sustained Cold Weather
(--0°
°°
° F & below)
Same Joist
Space
FRONT VIEW
SIDE VIEW
12²
²²
² MIN.