Wiegand Reader Connection (Entry / Exit)
In multiple reader mode, the secondary card reader has all connections wired to the same reader port as the
primary reader, except the Data 1 connection which is wired to the Data 1 input on the alternate reader port.
The normal primary reader connection operates as the entry reader, and the secondary reader that is multiplexed
into the alternate reader port will operate as the exit reader.
1 2
3 4
5 6
7 8
9 0
X
L1L2
BZ
C
D0/D1/
NANB
V+
V-
L1L2
BZ
C
D0/D1/
NANB
V+
V-
Entry Reader Connections
Color Wire Connection
Red V+ 12VDC positive
Black V- 12VDC negative
Green D0/NA Wiegand Data 0
White D1/NB Wiegand Data 1
Brown L1 LEDcontrol
Blue BZ beeper control
Shield Join the shield (drain) wires together. Frame grounded at one point only