sERVICINg
Independent + Combi - Installation and Servicing
4
3G9931
50
CONDENsa TE TRap/sIphON REpLaCEMENT
51
MaIN pCB REpLaCEMENT
* Note. that production boiler PCB’s are factory pre-
set to operate for boiler range and output, but when
ordering Primary PCB as a spare, an additional Boiler
Chip Card (BCC) MUST also be purchased for your
specic boiler range and output.
Note. Fit the earth strap provided with the PCB to
your wrist and secure to a suitable earth on the boiler
chassis.
1. Refer to Frame 40.
2. Note the control knob positions.
3.
Remove the 2 screws retaining the control box cover.
4. Carefully lift the 4 retaining clips and remove
control box cover.
5. Unplug all lead connections to the PCB including
the ribbon cable (to facilitate ribbon cable removal,
ease side clips apart and pull upwards), also where
applicable, push the small plastic clip with an
electrical screwdriver to facilitate plug removal.
6. Spring out the two side retaining clips and pull the
PCB upwards to clear the 4 corner retaining posts.
7. Take the new Primary PCB and attach the
appropriate Boiler Chip Card (BCC) to it (this
should correspond to the output of the boiler:
24kW, 30kW or 35kW). Note. Ensure the
correct orientation of BCC by placing “TOP” side up
as shown.
8. Re-connect all plug connections.
9. Reassemble in reverse order.
10. a. Turn power on
b. Displays “8” blue light on/off, “rst digit input”,
“second digit input”, “1st letter appliance type”,
i.e. “2”, “4”, “c”
c. Move knob to required setting (standby,
summer, winter)
Note. If no BCC tted on non programmed board
items a & b will be displayed then “Boiler Type Card
Fault - Contact Installer” The correct BCC for this
appliance will need to be tted.
11.
Check operation of the boiler. Refer to Frames 29 & 30.
3
3
6
5
2
Siphon
Ribbon Cable Connection
7
Plastic
Clip
5
1. Refer to Frame 40.
2. Pull off the rubber pipe at
the sump drain.
3. Disconnect the condensate
drain pipe.
4. Turn the siphon clockwise
to disengage and lift to
remove.
Note. Keep siphon upright
when removing
5. Clean siphon with water.
6. Re-assemble in reverse
order.
7. When re-assembling ensure the trap is full of water.
8. Check operation of the boiler. Refer to Frames 29 & 30.
sERVICINg
Unit 3A, Thornton Road Ind. Estate Off Hockney Road Bradford, BD8 9HQ
01274 488 388
www.heatingspares247.com