INSTALLATION
Project Heat - Installation and Servicing
FLUE OUTLET
18
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED
IMPORTANT. The boiler must be installed in a vertical position in accordance to the installation instructions.
FLUE KITS
Telescopic Flue‘B’ Pack - contains: Flue turret, telescopic ue incorporating a terminal and rubber wall seals.
Horizontal Flue Terminal (600mm long) ‘B’ Pack - contains: Flue turret, non telescopic single piece ue incorporating a terminal
and rubber wall seals.
Horizontal Flue Terminal (1000mm long) ‘B’ Pack - Flue turret, telescopic ue incorporating a terminal, rubber wall seals and instructions.
Note. If ‘B’ packs are used on their own (either 1 piece or telescopic), then they can be tted horizontally as the ue inside is
designed to slope 1.5 degrees.
‘D’ Pack - contains: 1 metre length of ue pipe (Functional length 950mm), 1 support bracket and instructions.
When extension ‘D’ Packs are used the ue duct must incline 1.5 degrees away from the appliance, to allow the condensate to drain
back to the boiler and out of the condensate drain. It is recommended that a support bracket is tted on every 1 metre of pipe work
used and the bracket is located as close to the collar as possible. The bracketing must ensure a 1.5 degree fall back to the appliance.
Optional Flue Finishing Kit - UIN 155988 & Concentric Flue Screw Retaining Kit (Optional Kit of mechanical xing of ue joints)
Only use water as a lubricant during assembly.
The ‘B’ pack terminal is classed as part of the maximum ue length.
These ue systems incorporates a removable ue outlet nose that utilises a push t location system. This enables the installation
of deector, high level or balcony ue kits without the removal of the whole ‘B’ pack terminal. The appliance must not be operated
without the desired outlet nose correctly tted in place, ensuring the side location dimples are in line with the mounting face
allowing the correct sealing of the components.
It is IMPORTANT that all attachments are tted in accordance to the installation instructions provided with them.
The TURRET supplied in the ‘B’ Pack has an upper combustion sample point with a screw cap seal and a lower air sample point
with an air stopper seal. Ensure all caps & seals are in place.
Additional Termination Kits available for use with these ‘B’ packs.
Flue Deector Kit The resistance is the equivalent of 1 metre of ue pipe and therefore must be deducted from
any maximum ue length
High Level Flue Outlet Kit
The maximum permissible concentric ue length when using a standard (500mm) kit is 4.5 metres
Balcony Flue Outlet Kit The maximum permissible concentric ue length when using this kit is dependant on the length
of the balcony ue outlet run which combined with the concentric run must not exceed the
maximum ue length requirement of the appliance it is to be tted to
Total Maximum Permissible Horizontal Concentric Flue Length combining both ‘B’ Packs and ‘D’ Packs
(Measured from centreline of the turret to the outside of the wall terminal)
15 & 24 kW appliances Total Maximum: 9 metres - minus any ue kit options or bends
Total Maximum Permissible Vertical Flue Length combining both Roof Terminal and ‘D’ Packs
15 & 24 kW Appliances Total Maximum (60/100): 7.5 Metres - minus any bends
REAR FLUEING This is dedicated ue with no removeable nose section.
Total Maximum Permissable Rear Flue Length
15 & 24 kW Appliances Total Maximum (50/80) - 442mm - No additional bends etc allow
15 & 24 kW Appliances Total Minimum (50/80) - 115mm - No additional bends etc allow
Dedicated High Level Flue Outlet
Kit - see kit instruction for furher
details
(50/80) - Maximum Vertical Run - 15 & 24 kW - 11M