INSTALLATION
Project Heat - Installation and Servicing
FLUE OUTLET
19
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED........CONT’D
(Equivalent ue length resistance = 1M)
 - (Equivalent ue length resistance = 0.6M)
Minimum Horizontal Flue Lengths (Centre line of turret to outside of wall terminal)
Telescopic Flue ‘B’ Pack = 400mm
Horizontal Flue terminal (600mm long) ‘B’ Pack = 285mm
Wall Thickness Std Metric Brick 102.5mm wide
‘B’ Pack Flue Type 60/100 Minimum permissible Wall Thickness Maximum permissible Wall Thickness
Rear Flue Side Flue Rear Flue Side Flue
Horizontal Flue Terminal
(600mm long) B Pack
116 102.5 501 456
Telescopic Flue B Pack 231 186 429 384
Horizontal Flue Terminal
(1000mm long) B Pack
546 501 761 716
Horizontal Flue Terminal
(1000mm long) B Pack cut 75mm
471 426 686 641
For Flue lengths between 658 & 708 use a Horizontal Flue Terminal (1000mm long) B Pack, cut 75mm off the end of the

100mm
Edge of turret
to outside face of wall plus
44mm = ue length
Centre of turret to edge of turret = 100mm
Turret has a ue insertion of 30mm
The compressed outer wall seal has protruding wall to seal mounting lip - 14mm
From centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mm
NOTES
REAR
Fit
to wall
A
WALL
Flue length measured from outer terminal lip
to end of outer ue
A + 44mm
Edge of turret
to outside face of wall plus
44mm = ue length
SIDE
Fit
to wall
A
WALL
Minimum clearance 5mm
20
DETERMINING THE FLUE LENGTH AND FLUE PACKS REQUIRED, CONT’D
Shows the ue required when measured from outside edge of turret to the outside face of the wall (to obtain cut length add 44mm)

Horizontal Flue Terminal
(600mm long) B Pack
Telescopic Flue B Pack Horizontal Flue
Terminal (1000mm long)
B Pack (Telescopic)
Horizontal Flue Terminal
(1000mm long) B Pack
(Telescopic) Cut 75mm
Minimum Maximum Minimum Maximum Minimum Maximum Minimum Maximum
B Pack (Standard) 171 556 286 484 601 816 526 741
Plus 1 (1m D pack) 1121 1506 1236 1434 1551 1766 1476 1691
Plus 2 (1m D pack) 2071 2456 2186 2384 2501 2716 2426 2641
Plus 3 (1m D pack) 3021 3406 3136 3334 3451 3666 3376 3591
Plus 4 (1m D pack) 3971 4356 4086 4284 4401 4616 4326 4541
Plus 5 (1m D pack) 4921 5306 5036 5234 5351 5566 5276 5491
Plus 6 (1m D pack) 5871 6256 5986 6184 6301 6516 6226 6441
Plus 7 (1m D pack) 6821 7206 6936 7134 7251 7466 7176 7391
Plus 8 (1m D pack) 7771 8156 7886 8084 8201 8416 8126 8341
Plus 9 (1m D pack) 8721 9000 8836 9000 9000 9000 9000 9000
Max output 15 & 24 kW
FIGURE 1
FIGURE 2
Note. Maximum permissible
ue length is measured from
centre line of appliance ue
outlet to outside wall face.
Note; Telescopic ue B Pack or attached “D” pack extensions do not need to be cut between minimum and maximum values shown above (except
where specied). Horizontal Flue Terminal (600mm long) B Pack ue will require cutting on values below maximum values shown in the table above.