EasyManua.ls Logo

IFM Electronic DTE101 - Operating and Display Elements; 7�1 Reset to Factory Settings; 7�2 LED Indicators; 7�2�1 Led Aux

IFM Electronic DTE101
19 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
UK
7 Operating and display elements
7.1 Reset to factory settings
The Ethernet parameters can be reset to the factory settings� Take the following
steps:
Remove all cable connections from the device�
Insert an electrically conductive bridge between pin 1 and pin 3 on the process
connection IO-3�
Connect device with the voltage supply and wait until the yellow LED indication
on AUX and IO-3 flashes at approx� 8 Hz�
Disconnect the device from the voltage supply and connect it again�
> The settings are reset�
7.2 LED indicators
The device indicates the current status of the interface via the status LEDs�
7.2.1 LED AUX
LED green LED yellow Status Note
Off Off No voltage supply U
AUX
< 5 V
On
Flashes at
2 Hz
Voltage supply too low 5 V ≤ U
AUX
≤ 18 V
On Off Voltage supply OK 18 V ≤ U
AUX