6.2 Cable routing in control cabinets
Install network/bus cables in separate cable ducts or separate cable bundles�
Where possible, do not install network/bus cables parallel to power supply
lines�
Install network/bus cables at least 10 cm away from power lines�
6.3 Installation instructions
Electrostatic discharge
The device contains components that can be damaged or destroyed by
electrostatic discharge�
When handling the device, observe the necessary safety precautions against
electrostatic discharge (ESD) according to EN 61340-5-1 and IEC 61340-5-1�
In order to eliminate electrostatic charges, the device may only be operated on
a grounded DIN rail�
7 Electrical connection
The national and international regulations for the installation of electrical
equipment must be adhered to� Avoid contact with dangerous contact voltages�
► Disconnect power.
► Connect device, connection via COMBICON connectors (pre-mounted).
► To prevent negative effects on the functions caused by noise voltages, lay
sensor cables and load cables separately� Maximum length of the sensor cable:
250 m�
Use a screened sensor cable�
The outputs are short-circuit proof and can be configured as either normally closed
or normally open�
In addition an analogue signal can be provided on output [OU 1] (0/4���20 mA) (e�g�
acceleration values)�