STV75 ed 01/08 VICTRIX 75
Code Description Remedy
b 18 System ow temperature higher than 92°C
Check the circulation of water in the
system
b 19 System return temperature higher than 87 °C
Check the circulation of water in the
system
b 24 Flow and return probes inverted Check probes position
b 25 System ow temperature increases too quickly
Check the circulation of water in the
system
b 26 No water
Check the correct pressure of the water
inside the system
Bring the water pressure in the system to
value between 1 and 1.2 bar
Check for leakage in the circuit
b 28 Fan failure (no Hall signal)
Check the fan
Check "F3" fuse
Check circuit board
b 29 Fan failure
Check the fan
Check "F3" fuse
Check circuit board
b 30
Dierence between system ow and return temperature higher
than 40 °C
Check the circulation of water in the
system
b 33 Domestic hot water probe failure (short circuited) Check / replace DHW probe
b 38 Domestic hot water probe failure (open) Check / replace DHW probe
b 65 Waiting for the fan to start (insucient air ow) Check fan function
b 118
Loss of ionising current during burner ignition (after 3 attempts,
fault becomes error "02" ignition inhibition)
Check gas and electricity supplies
Check gas supply pressure
Indications and malfunctions with electrical rearming.
e board features a display that shows malfunctions or shut-
downs by means of error codes.
e error codes preceded by the letter “bare temporary shut-
downs (volatile) so, if the conditions that caused the shutdown
stop, the boiler rearms itself automatically and starts working
normally again.
19 System return temperature too high (over 87 °C)
Check the circulation of water in the
System
25 System ow temperature increase too rapid
Check water ow in system
Check primary heat exchanger
30 Dierence between ow and return temperatures too high Check water ow in system
31 System ow probe failure (short circuited) Change the system ow probe
32 System return probe failure (short circuited) Change the system return probe
36 System ow probe failure (open) Change the system ow probe
37 System return probe failure (open) Change the system return probe
114 Invalid cascade address
Check address set on board (See cascade
and zone adjuster helper board)