STV75 ed 01/08 VICTRIX 75
Technical specications.
Technical specications, VICTRIX 75.
- e ue temperature values refer to an inlet temperature of
15°C and a ow temperature of 50°C.
- e maximum sound power emitted while the boiler is
working is < 55dBA. is measurement refers to tests in a
semi-anechoic chamber with the boiler working at maximum
heat output and with the extension of the ue accessories
complying with product standards.
Nominal heat input kW (kcal/h) 74.6 (64169)
Minimum heat input kW (kcal/h) 18.5 (15949)
Nominal (useful) heat output kW (kcal/h) 72.6 (62436)
Minimum (useful) heat output kW (kcal/h) 18.1 (15566)
Eective eciency 80/60 Nom./Min. % 97.3 / 97.6
Eective eciency 50/30 Nom./Min. % 104.5 / 106.3
Eective eciency 40/30 Nom./Min. % 107.0 / 107.0
Casing losses with burner On/O (80-60°C) % 0.32 / 0.40
Chimney losses with burner On/O (80-60°C) % 0.01 / 2.30
Maximum working pressure of heating circuit bar 4.4
Maximum working temperature of heating circuit °C 90
Heating temperature adjustment °C 20 - 85
Available head with 1000/h ow rate kPa (m H
2
O) 65.5 (6.68)
Full boiler weight kg 72
Empty boiler weight kg 68
Generator water capacity l 4
Power supply connection V/Hz 230/50
Nominal power input A 1.26
Installed electrical power W 270
Pump power absorption W 168
Fan power absorption W 72
Appliance electrical insulation - IPX5D
Max. ambient operating temperature °C +50
Min. ambient operating temperature °C -5
Min. ambient operating temperature with (optional) antifreeze kit °C -15
Max. ue gas temperature °C 75
NO
X
class - 5
Weighted NO
X
mg/kWh 50
Weighted CO mg/kWh 43
Type of appliance C13 / C33 / C63 / B23 / B33