Conformity to the Low Voltage Directive in the EU (Continued)
11. Use wires listed in EN60204 Appendix C.
MCCB: Moulded case circuit breaker
RDC: Residual-current-operated protective device
ELCB: Earth leakage circuit breaker
Notes 1) A box (
) in the above table replaces E suffix for filtered version.
*1 The frame size and model of the MCCB or RCD/ELCB (with the exception of those exclusively
designed for protection from ground faults) will vary, depending on the power transformer capacity.
Refer to the related technical documentation for details.
*2 The recommended wire size for main circuits is for the 70qC 600V PVC wires used at an ambient
temperature of 40qC.
*3 Wire sizes are calculated on the basis of the input current under the condition that the power supply
capacity and impedance are 500 kVA and 5%, respectively.
Recommended wire size (mm
2
)
*1
Rated current (A)
of
MCCB or RCD/ELCB
*2
Main circuit
power input
[L1/R, L2/S, L3/T]
[L1/L, L2/N]
Grounding [
G]
Power supply voltage
Appli-
cable
motor
rating
(kW)
Inverter type
w/ DCR
*3
w/o DCR
w/ DCR
*3
w/o DCR
*2
Inverter
output
[U, V,
W]
*2
DCR
[P1,
P (+)]
Braking
resistor
[P (+),
DB]
Control
circuit
(30A,
30B,
30C)
0.4 CUB3A-2 6
0.75 CUB5A-2
6
10
1.5 CUB8A-2 16
2.2 CUB11A-2
10
20
2.5 2.5
Three-phase
200 V
3.7 CUB17A-2 20 35
2.5
4 4
2.5 0.5
0.4 CUB1A5-4
0.75 CUB2A5-4
6
1.5 CUB3A7-4
6
10
2.2 CUB5A5-4 16
Three-phase
400 V
4.0 CUB9A-4
10
20
2.5 2.5 2.5 2.5 0.5
0.4 CUB3A-1
10
0.75 CUB5A-1 10 16
2.5
1.5 CUB8A-1 16 20
2.5
4
2.5 2.5 0.5
Single-phase
200V
2.2 CUB11A-1 20 35 4 6 4