10 Troubleshoong
Below are the possible causes of failure or malfuncon with an explanaon of
measures to be taken. In the event of defects not contained in the table or in the
event of faults that cannot be resolved following the contained instrucons, contact
Indel Webasto Marine S.r.l. directly.
Table 8: Fault-cause-measure summary table
Fault Possible cause Measure
Nothing happens when the
power is switched on.
Incorrect polarity.
No electrical current.
The baery is drained.
Voltage drop due to cables that
are too thin.
Thermostat fault
Electronic unit fault
Correctly posion + and - con-
necons.
Check that mains power is
connected.
Check fuses.
Inspect the charging circuit.
Check possible voltage drops.
Replace cables if necessary.
Connect to bridge C and T on the
electronic unit. If the compres-
sor starts up, the thermostat is
faulty.
Change the electronic unit.
The compressor only performs
brief start aempts at start-up.
Power problems, voltage too low
or voltage drop during start-up
aempts.
The Baeries are drained.
Check cables and connecons,
possible presence of verdigris.
Charge the baeries, start the
motor or connect the baery
charger.
The compressor funcons but
does not cool.
Loss of refrigerant.
Quick coupling joints not ght-
ened enough.
Hoses or evaporator leaking.
Insect and ghten. Contact an
expert in refrigeraon systems
for a general check or a specic
refrigerant check.
The compressor runs for a long
me but without generang
enough cold.
Inadequate venlaon and/
or insucient insulaon of the
compressor.
Improve venlaon and/or
isolaon of the cooling compart-
ment.
The compressor runs too long,
generang too much cold in the
cooling compartment.
The end of the thermostat
sensor is not mechanically con-
nected to the evaporator.
The thermostat has a fault for
which it does not turn o.
Check assembly of the sensor
end and replace it.
Re-posion the thermostat.
Fuses are blown.
Fuses are sized incorrectly.
Electronic unit fault
Check fuses 15 A – 12 V / 7.5
A – 24 V
Change the electronic unit.
User Manual