Parameter 2: Select “Add” or Sub” function to
calibrate battery voltage to real figure.
Parameter 3: The voltage setting range is from
0V to 5.7V. The default value is 0V.
14: reserved
Interface
Setting
reserved
15: Inverter voltage calibration
Interface
Setting
Parameter 2: you may choose Add or Sub to
calibrate inverter voltage
Parameter 3: The voltage setting range is from
0V to 6.4V. The default value is 0V.
16: Floating charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to
adjust floating charger voltage.
Parameter 3: the voltage range is from 0V to
6.4V, the default value is 0V.
17: Constant charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to
adjust constant charger voltage.
Parameter 3: the voltage range is from 0V to
3.2V, the default value is 0V.
18: Maximum charger current setting