EasyManua.ls Logo

INIM PREVIDIA MICRO - CE Mark and Standards Compliance

INIM PREVIDIA MICRO
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 General information
Fire alarm and extinguishing system
Level 3: Programming - this access level is for specialized technical operators who carry out system configuration,
commissioning and maintenance.
Access requires entry of a valid access code with sufficient access rights after inserting a jumper which enables
programming. Refer to the manual for system configuration, commissioning and maintenance.
ONLY authorized technicians, appointed by the Manufacturer can, by means of special tools, carry out repair work on
the motherboard.
Level 4: only authorized technicians, appointed by the Manufacturer can, by means of special tools, carry out repair
work on the motherboard.
1.4 CE Mark
1.4.1 Regulation (EU) No. 305/2011
This product complies with requirements stated by standards listed here below in compliance with Regulation (EU) No. 305/2011.
0051
INIM Electronics s.r.l.
Via Dei Lavoratori 10 - Fraz. Centobuchi
63076, Monteprandone (AP) - Italy
23
0051-CPR-3155
EN 54-2:1997 + A1:2006
EN 54-4:1997 + A1:2002 + A2:2006
EN 54-21:2006
EN 12094-1:2003
PREVIDIA-MLZEG
Control and indicating equipment with power supply equipment, alarm
transmission and fault warning routing equipment and electrical automatic
control and delay device integrated for fire detection and fire alarm systems
installed in buildings and for gas extinguishing systems installed in
buildings and part of a complete system.
0051
INIM Electronics s.r.l.
Via Dei Lavoratori 10 - Fraz. Centobuchi
63076, Monteprandone (AP) - Italy
23
0051-CPR-3156
EN 54-2:1997 + A1:2006
EN 54-4:1997 + A1:2002 + A2:2006
EN 54-21:2006
EN 12094-1:2003
PREVIDIA-MSZEG
Control and indicating equipment with power supply equipment, alarm
transmission and fault warning routing equipment and electrical automatic
control and delay device integrated for fire detection and fire alarm systems
installed in buildings and for gas extinguishing systems installed in
buildings and part of a complete system.
Essential features
Performanc
e
Performance in the event of fire
PASS
Power supply performance
PASS
Response delay (response time in the event of fire)
PASS
Transmission performance
PASS
Operating reliability
PASS
Durability of
operating reliability:
Thermal resistance
PASS
Vibration resistance
PASS
Humidity resistance
PASS
Electrical stability
PASS
Options provided in accordance with EN54-2
Performanc
e
7.8 Output to fire alarm devices
PASS
7.9 Output to fire alarm routing equipment
PASS
7.10 Output to fire protection equipment
PASS
7.11 Delay on outputs
PASS
7.12 Co-incidence detection (Type A, B and C)
PASS
7.13 Alarm counter
PASS
8.9 Output to remote fault or warning signalling devices
PASS
10.0 Test condition
PASS
Options provided in accordance with EN12094-1
Performanc
e
4.17 Delay of extinguishing signal
PASS
4.18 Signal representing the flow of extinguishing agent
PASS
4.19 Monitoring of the status of components
PASS
4.20 Emergency hold device (*)
PASS
4.21 Control of flooding time
PASS
4.23 Manual only mode
PASS
4.24 Triggering signals to equipment within the system
PASS
4.26 Triggering of equipment outside the system
PASS
4.27 Emergency abort device (*)
PASS
4.30 Activation of alarm devices with diverse signals
PASS
(*) one only between 4.20 and 4.27
Additional information according to EN 54-2
About information required at point 12.2.1, see data contained in this
manual.
Additional information according to EN 54-4
About information required at point 7.1, see data contained in this manual.
Additional information according to EN 54-21
For the information required by point 7.2.1, see data contained in this
manual.
Additional information according to EN 12094-1
Environmental class: A
Degree of protection: IP30
Flooding zones: 1
Zones for CO2, inert gas or halogenated hydrocarbons.
Response delay activation condition: max 3s
Response delay triggering of outputs: max 1s

Other manuals for INIM PREVIDIA MICRO

Related product manuals