3 Electrical Installation
3.1 Cable Selection
Communication Wiring
EtherCAT bus communication adopts shielded Ethernet cables for data transmission,
without short circuit, misalignment and poor contact. The length of cables between
devices cannot exceed 100m; otherwise, signal attenuation will occur and affect
normal communication. It is recommended to use cables specified as follows.
Item Specification
Cable type Elastic crossover cable, S‑FTP, Cat5
Standard EIA/TIA568A, EN50173, ISO/IEC11801
EIA/TI Abulletin TSB, EIA/TIA SB40‑A&TSB36
Cross sectional area AWG26
Conductor type Twisted pair
Pair 4
Power Supply Wiring
The cable lug and cable diameter included in the following table are only for
reference.
Material
Name
Applicable Cable Diameter KST Suzhou Yuanli
mm
2
AWG Model Crimping
Tool
Model Crimping
Tool
Tubular
lug
0.3 22 E0308 KST2000L 0308 YAC‑5
0.5 20 E0508 0508
0.75 18 E7508 7508
1.0 18 E1008 1008
1.5 16 E1508 1508
If you use other types of tubular lug, crimp the lug to the cables according to the
shape and dimension requirements shown in the figure below.