Parameter Description MD280/MD280N User Manual
- 160 -
frequency which is higher than 85Hz.
Fast current limit
function selection
Factory
default value
1
0 Invalid
F5-20
Setup
range
1 Valid
Enable the fast current-limit function so as to minimize inverter overcurrent
protection fault and make the inverter work normally.
When entering the fast current-limiting state to continue for some time, will
report fast-limit overtime fault (Err40), which indicates the inverter is
overload, and refer to the process of Err10.
Caution:
Please do not use this function for the hoist type of load, other load is
recommend to use this function.
Wake-up
frequency
Factory default
value
0.00Hz
F5-21
Setup range
Sleep frequency to maximum
frequency˄F0-04˅
Wake-up delay
time
Factory default
value
0.0s
F5-22
Setup range 0.0s to 6500.0s
Sleepfrequency
Factory default
value
0.00Hz
F5-23
Setup range
0.00Hz to wake-up frequency˄F5-21˅
Sleep delay
frequency
Factory default
value
0.0s
F5-24
Setup range 0.0s to 6500.0s
This function can achieve the sleep and wake-up function. After the running
the command, if it is in Sleep state when the setup frequency is not less
than F5-21 (frequency), and then the inverter begins to start after the
wake-up delay time of F5-22.During the operation, when the setup
frequency is not more than F5 -23 (Sleep frequency), and then the inverter
stops after the wake-up delay time of F5-24.Set F5-21 (wake-up
frequencies) and 5-23 (Sleep frequency) to 0, which indicates that the
Sleep and wake-up is invalid.
Caution:
When use the Sleep function, please ensure whether to operate the
function code of F6-10(PID operation mode) when stopping.