Parameter Description              MD280/MD280N User Manual 
- 180 -
Motor Overload Protection
Gain Coefficient 
Rated Curre
Time 
60 min
1 min
Motor Overload Protection
Gain Coefficient 
Rated Curre
Time 
60 min
1 min
 
 
Fig6- 25 Schematic Diagram for inverse time-lag curve of overload protection on motor 
 
Motor overload 
prealarm coefficient 
Factory default 
value 
80% 
FB-02 
Setup range  50% to 100% 
When the motor overload detection level reaches this parameter setup 
value, the multifunctional output terminal DO or fault relay (RELAY) will 
output motor overload prealarm signal. This parameter is calculated 
according to the percentage of time for continuous running under certain 
overload point rather than the overload fault time percentage.   
For example, the motor overload protection gain is set to 1, the motor 
overload prealarm coefficient is set to 80%, when the motor keeps running 
for 48 seconds (80%×one minute) under 220% of rated current, the 
multifunctional output terminal DO or fault relay (RELAY) will output motor 
overload prealarm signal. 
Ovter voltage stall gain 
Factory 
default value
0 
FB-03 
Setup range  0 to 100   
Over voltage stall protection 
voltage 
Factory 
default 
value 
130% 
FB-04 
Setup range  120% to 150% 
Over-voltage stall gain: It adjusts the inverter’s capacity in suppressing the 
current stall. The bigger the value is, the stronger the capacity is. For the 
load with small inertia, the value should be small. Otherwise, the dynamic 
response of the system will be slow. For the load with large inertia, the 
 