MD280/MD280N User Manual             Parameter Description          
- 181 -
value should be large. Otherwise, the suppressing result will be poor, and 
over voltage fault may be caused.   
Over voltage stall protection voltage: It selects the protection point for over 
voltage stall function. When the value is exceeded, the inverter starts to 
execute the over voltage stall protection function. 
Over current stall gain 
Factory 
default value
20 
FB-05 
Setup range  0 to 100 
Over current stall 
protection current 
Factory default 
value 
150% 
FB-06 
Setup range  100% to 200% 
Over current stall: When the output current of the inverter reaches setup 
over current stall protection current (FB-06), if the inverter is running with 
acceleration speed, it will stop acceleration. When the inverter is running 
with constant speed, it will reduce the output frequency. When the inverter 
is running with deceleration speed, it will stop deceleration and the 
operating frequency will not recover normally till the current is less than the 
current stall protection current (FB006). Please refer to Fig.6-23 for details.   
 
Over current stall protection current: It selects the protection point for over 
current stall function. When the value is exceeded, the inverter starts to 
execute the over current stall protection function. This value is relative to 
the percentage of rated current of the motor.   
 
 
Over current stall gain: It adjusts the inverter’s capacity in suppressing the 
over current stall. The bigger the value is, the stronger the capacity is.   
 
 