6. Description of Parameters
- 126 -
6
Function Code Parameter Name Setting Range Default
FA-03
PID operation direction 0: Forward
1: Reverse
0
FA-04
PID reference and
feedback range
0 to 65535 1000
FA-05
Proportional gain Kp1 0.0 to 100.0 20.0
FA-06
Integral time Ti1 0.01s to 10.00s 2.00s
FA-07
Differential time Td1 0.00s to 10.000s 0.000s
)$VHWVGLUHFWLRQRI3,'RSHUDWLRQ,WLVLQÀXHQFHGE\',IXQFWLRQ3,'RSHUDWLRQ
direction reverse".
Ɣ
FA-03 = 0: Forward
When PID feedback is smaller than PID reference, the AC drive increases output
frequency. The winding tension control requires forward PID operation.
Ɣ
FA-03 = 1: Reverse
When PID feedback is smaller than PID reference, the AC drive decreases output
frequency. The unwinding tension control requires reverse PID operation.
FA-04: It is a non-dimensional parameter and is used for calculating display of PID
reference (U0-15) and PID feedback (U0-16).
Ɣ
U0-15 = PID reference (percentage) x FA-04
Ɣ
U0-16 = PID feedback (percentage) x FA-04
For example, if FA-04 is set to 2000 and PID reference is 100.0%, display of PID
reference (U0-15) is 2000.