6. Description of Parameters
- 202 -
6
Ƶ
FWD/REV Switchover Dead-zone Time
Figure 6-57 Forward/Reverse run switchover dead-zone time
Output frequency (Hz)
Forward run
Reverse run
Dead-zone time
Function Code Parameter Name Setting Range Default
F8-12 Forward/Reverse run
switchover dead-zone time
0.0s to 3000.0s 0.0s
Ƶ
Reverse Run Prohibited
Figure 6-58 Control of reverse run
Frequency
reference
0
1
F8-13
0
1
0
1
F0-09
Motor
runs in FWD direction
runs in REV direction
runs in REV direction
runs in FWD direction
runs at 0.0 Hz
> 0
0
Frequency
reference
Frequency
reference
0
Frequency
reference
> 0
Reverse RUN command
(terminal, communication)
0
1
RUN command
(operation panel)
Forward RUN command
(terminal, communication)
Function Code Parameter Name Setting Range Default
F8-13 Reverse RUN
selection
0: Enabled
1: Disabled
0
F0-09 Running direction 0: Run in the default direction (FWD/REV
indicator off)
1: Run in the direction reverse to the
default direction (FWD/REV indicator on)
0
Note
The original direction of motor will be resumed after parameter initialization.
Do not use this function in applications where changing rotation direction of
motor is prohibited after system commissioning is completed.