Appendix
- 335 -
12
Para. No. Para. Name Setting Range Default Property Page
A1-10 Active state selection for AI used
as DI
000 to 111
AI2
0: High level active
1: Low level active
AI1
0: High level active
1: Low level active
AI3
0: High level active
1: Low level active
000
ƿ
1
8
9
A1-11 VDO1 function selection 0: No output
1: AC drive running
2: Fault output
3: Frequency level detection 1
output
4: Frequency reached
5: Zero-speed running (no output
at stop)
6: Motor overload pending
7: AC drive overload pending
8: Set count value reached
9: Designated count value
reached
10: Length reached
11: PLC cycle completed
12: Accumulative running time
reached
13: Frequency limited
15: Ready for RUN
16: AI1 > AI2
17: Frequency upper limit
reached
18: Frequency lower limit reached
(no output at stop)
19: Undervoltage
20: Communication setting
21: Reserved
22: Reserved
23: Zero-speed running 2 (having
output at stop)
24: Accumulative power-on time
reached
25: Frequency level detection 2
26: Frequency 1 reached
27: Frequency 2 reached
28: Current 1 reached
29: Current 2 reached
30: Timing reached
31: AI1 input exceeding limit
32: Load lost
33: Reverse running
0
ƿ
1
8
8
A1-12 VDO2 function selection 0
ƿ
1
8
8