3. Electrical Installation
- 56 -
3
In
F
i
g
u
r
e
3
-
7
,
the side entry copper bar can be removed if necessary. Dimensions of main
circuit terminals without side entry copper bar are shown below.
Figure 3-8 Terminal dimensions of MD290T200G-L, MD290T220G-L and MD290T220P-L to
MD290T280P-L (without side entry copper bar, without output reactor)
300
35
161.5
60
35
135
62
33
33
14-M12
S
R
T
U
V
W
236.5
85
50
48.5
31.5
2 13
Table 3-7 Recommended cable dimensions and tightening torque of MD290T200G(-L),
MD290T220G(-L) and MD290T220P(-L) to MD290T280P(-L)
AC Drive Model Rated Input
Current (A)
Power Input/
Output Cable
Crimp
Terminal
Model
Ground
Cable
Crimp
Terminal
Model
Tightening
Torque (N·m)
Screw
Spec.
MD290T200G(-L) 365 2 x (3 x 95) mm
2
4/0 AWG x 2P
100-12 95 mm
2
1 AWG
60-12 35.0 M12
MD290T220P(-L) 410 2 x (3 x 120) mm
2
300 kcmil x 2P
150-12 120 mm
2
1/0 AWG
60-12 35.0 M12
MD290T250P(-L) 456 2 x (3 x 120) mm
2
300 kcmil x 2P
150-12 120 mm
2
1/0 AWG
60-12 35.0 M12
MD290T220G(-L) 410 2 x (3 x 120) mm
2
300 kcmil x 2P
150-12 120 mm
2
1/0 AWG
60-12 35.0 M12
MD290T280P(-L) 507 2 x (3 x 150) mm
2
400 kcmil x 2P
200-12 150 mm
2
1/0 AWG
60-12 35.0 M12