34
Setting value Function Description
19
UP/DOWN setting
clearance (terminal and
keypad)
When the frequency reference is digital frequency reference, this
terminal may be used to clear the frequency value changed by the
UP/DOWN button and restore the reference frequency to the value
set in F0-04.
20
Switching terminal for
running commands
When F0-01 is set as “1”, this terminal can be used to switch between
the terminal control and the key control.
F0-13 DO selection (Open collector output terminal)
Default 1 (the invert is running)
Setting value Function Description
0
No output The output terminal has no function
1
Invert is running
It indicates that the inverter is running with output frequency. At this point,
there is ON signal output.
2
Fault output When the inverter is faulty, ON signal will be output.
3
Preset frequency
arrived
See the details of the function code F6-10.
AO output selection
Default
0
F0-14
The AO terminal is used as the analog voltage output terminal, and the common potential is COM.
The output voltage ranges from 0 ~ 10VDC.
Setting value Function Range
0
Running frequency 0 ~ maximum output frequency
1
Setting frequency 0 ~ maximum output frequency
2
Output current 0 ~ 2×rated current of inverter
3
PULSE input 0.0 ~ F3-10
4
Panel potentiometer 0V ~ 10V
5
AI 0V ~ 10V/0V ~ 24V/(0mA ~ 20mA)
F0-15 Start mode
Default
0
0
Direct start (when the DC braking start time is not “0”, the DC braking is
enabled prior to the start)
Setting
range
1 The rotational speed search is enabled prior to the start
0: Direct start
Start with start frequency
1: The rotational speed search is enabled prior to the start
The inverter first judges the rotational speed and direction of the motor and then outputs voltage
corresponding to the direction and speed of the motor. In this way, the motor can be started in a
smooth mode. It is applicable to restart for motor with high inertia after momentary power-off.
F0-16 Stop mode
Default 0
0 Deceleration stop Setting range
1 Coast to stop
0: Deceleration stop
Once the stop command is enabled, the inverter will reduce the output frequency according to the
deceleration mode and the defined acceleration/deceleration time. When the frequency is