35
decreased to “0”, the inverter will power off.
1: Coast to stop
After the stop command is enabled, the inverter will terminate the output immediately and the loads
will coast to stop with the mechanical inertia.
F1 Group: Motor Parameters
F1-00 Motor type selection
Default 0
0 Common asynchronous motor
1 Variable frequency asynchronous motor
Setting
range
2 Synchronous motor
F1-01 Rated power
Default Depending on inverter
model
Setting range 0.4kW ~ 1000.0kW
F1-02 Rated voltage
Default Depending on inverter
model
Setting range 0V ~ 440V
F1-03 Rated current
Default Depending on inverter
model
Setting range 0.00A ~ 655.00A
F1-04 Rated frequency
Default Depending on inverter
model
Setting range 0Hz ~ 3200.0Hz
F1-05 Rated rotation Velocity
Default 1460
Setting range 0rpm ~ 30000rpm
F1-06 Stator resistance
Default Depending on inverter
model
Setting range 0.001 ~ 65.535
F1-07 Rotor resistance
Default Depending on inverter
model
Setting range 0.001~ 65.535
F1-08 Leakage inductance
Default Depending on inverter
model
Setting range 0.01 ~ 655.35mH
F1-09 Mutual inductance
Default Depending on inverter
model
Setting range 0.1mH ~ 6553.5mH
F1-10 Excitation current
Default Depending on inverter
model
Setting range 0.01A ~ 650.00A
If the automatic tuning of the motor is completed normally, the values in F1-06 to F1-10 will be
updated automatically. The motor parameters will remain unchanged when recovering the factory
parameter setting with FP-01.
Each time the motor rated parameters (F1-01 to F1-05) are changed, the inverter will set the
parameters (F1-06 to F1-10) as default standard motor parameters (quadrupole Y series induction
motor).