44
Setting
range
100% ~ 200%
Select the protection value of the overcurrent stall
function. The inverter starts executing the overcurrent
stall protection function when this value is surpassed.
F5-06 Automatic fault reset times
Default 0
Setting
range
0 ~ 3
When the fault automatic reset function is selected for
the inverter, the times when the inverter can be
automatically reset is set. If this value is surpassed, the
inverter is faulty and stops, waiting for maintenance.
F5-07 Automatic fault reset interval
Default 1.0S
Setting
range
0.1s ~ 100.0s
The time interval between the beginning of the fault and
the implementation of automatic reset.
F5-08 Power loss compensation
Default 0
Setting range
0: Invalid
1: Invalid
If invalid, when the voltage decreases
transiently to the undervoltage point,
the inverter will alarm directly.
If valid, when the voltage decreases
to the undervoltage point, the inverter
will decelerate until the voltage
recovery.
F5-09 Inverter offload protection selection
Default 1
Setting
range
0: Disabled
1: Enabled
Select whether to protect when the offload occurs or not.
When selecting the offload protection function and there is
no load at the output end of the inverter, the output
frequency of the inverter will automatically reduce to 2Hz.
F5-10 Fault type
0 ~ 24
F5-11 Frequency at fault
Indicating the frequency when the latest fault
occurs
F5-12 Current at fault
Indicating the current when the latest fault
occurs
F5-13 Bus voltage at fault
Indicating the bus voltage when the latest
fault occurs
F6 Group: Auxiliary Function
F6-00 Maximum frequency
Default 50.0Hz
Setting range 50.0Hz ~ 3200.0Hz
It is used to set the maximum output frequency of the inverter.
F6-01 Frequency upper limit
Default 50.0Hz
Setting range Frequency lower limit F6-02 ~ Maximum frequency F6-00
It refers to the output frequency upper limit of the inverter.
F6-02 Frequency lower limit
Default 0.0Hz
Setting range 0.0 Hz ~ Frequency upper limit F6-01
It refers to the output frequency lower limit of the inverter.