6. Description of Parameters
- 162 -
Function Code Parameter Name Setting Range Default
A7-01
AC drive output
terminal control
source selection
00000 to 11111
0: AC drive control
1: PLC program control
00000
Units position: FMR (FM used as
digital output)
Tens position: Relay (T/A-T/B-TC)
Hundreds position: DO1
Thousands position: FMP (FM
used as pulse control)
Ten thousands position: AO1
A7-03
PLC program controls
the FMP output
0.0% to 100.0% 0.0%
A7-04
PLC program controls
the AO1 output
0.0% to 100.0% 0.0%
A7-05
Selection of PLC
program controlling
digital output
000 to 111
0: Disabled
1: Enabled
000
Units position: FMR
Tens position: Relay
Hundreds position: DO1
The base value of A7-03 is F5-09 (Max. FMP output frequency). The base value of
A7-04 is 10 V (voltage output) or 20 mA (current output).
4. Set running command
When F0-02 = 2 (the command source is communication) and A7-00 = 1 (the user
programmable card is enabled), drive running is controlled by setting of A7-08.
You can implement control of the AC drive via PLC program by operating
corresponding D component.
Function Code Parameter Name Setting Range Default
A7-08
Setting running command
via the user programmable
card
0 to 7
0: No command
1: Forward run
2: Reverse run
3: Forward jog
4:Reverse jog
5: Coast to stop
6: Decelerate to stop
7: Fault reset
0