6. Description of Parameters
- 94 -
6
F4-18 to F4-21 and F4-3 to F4-26 dene AI curve 2 and AI curve 3, respectively. AI curve
2 and AI curve 3 have the same function and usage as AI curve 1 does. Refer to
S
t
e
p
1
:
S
e
t
A
I
c
u
r
v
e
.
Figure 6-14 Set AI curve 2
AI
Corresponding
percentage
80
.
20.
0.00
2.
00
10.
00
F4-18
0.0
F4-20
F4-19
F4-21
0%
0%
V/mA V/mA
Function Code Parameter Name Setting Range Default
F4-18
AI curve 2 min. input 0.00 V to F4-20 0.00 V
F4-19
Corresponding percentage of
AI curve 2 min. input
-100.00% to 100.0% 0.0%
F4-20
AI2 curve max. input F4-18 to 10.00 V 10.00 V
F4-21
Corresponding percentage of
AI curve 2 max. input
-100.00% to 100.0% 100.0%
F4-23
AI curve 3 min. input 0.00 V to F4-25 0.00 V
F4-24
Corresponding percentage of
AI curve 3 min. input
-100.00% to 100.0% 0.0%
F4-25
AI curve 3 max. input F4-23 to 10.00 V 10.00 V
F4-26
Corresponding percentage of
AI curve 3 max. input
-100.00% to 100.0% 100.0%