6. Description of Parameters    
- 163 -
5.  Set frequency reference
When frequency reference setting channel is communication and A7-00 = 1 (user 
programmable card is enabled), frequency reference of the AC drive is determined by 
setting of A7-06. 
You can implement control of frequency reference of AC drive via PLC program by 
operating corresponding D component.
Function Code Parameter Name Setting Range Default
A7-06
Setting frequency reference 
via the user programmable 
card
-100.00% to 100.00% 0.00%
The base value of this parameter is F0-10 (Max. frequency).
6.  Set torque reference.
When torque reference setting channel is communication and A7-00 = 1 (user 
programmable card is enabled), torque reference of the AC drive is determined by 
setting of A7-07. 
You can implement control of torque reference of AC drive via PLC program by 
operating corresponding D component.
Function Code Parameter Name Setting Range Default
A7-07
Setting torque reference via 
the user programmable card
-200.0% to 200.00% 0.0%
The base value of this parameter is rated motor torque.
7.  Set user-dened faults.
When A7-00 = 1 (user programmable card is enabled), you can set user dened faults 
Err80 to Err89 by operating corresponding D component to change setting of A7-09 in 
the range of 80 to 89.
Function Code Parameter Name Setting Range Default
A7-09
Setting torque reference via 
the user programmable card
0: No fault
80 to 89: User dened fault 
code
0
If setting of A7-09 is out of 80 to 89, the setting will not take effect.