3. Electrical Installation
- 41 -
 ● Cable specication and installation of all cables connected to the drive output U, V, W 
must comply with local safety regulations and relevant IEC standards.
 ● To avoid risk of equipment damage or operating faults, do not connect capacitor or 
surge absorber to the output side of the AC drive.
 ● Long motor cables can contribute to electrical resonance caused by distributed 
capacitance and inductance. In some cases, this might cause equipment damage in 
the drive, in motor or in cables. To avoid these problems, install an AC output reactor 
close to the drive if cable is longer than about 100 m.
 ● If the cable support bracket is not used, screen/shield has to be directly grounded to 
the grounding (PE) terminal. Ensure pig tail of screen/shield is as short as possible.
 
■
Grounding (PE) Connection
Electrical Shock Hazard. Ensure the protective earthing conductor complies 
with technical standards and local safety regulations. Because the leakage 
current exceeds 3.5 mA in all models, IEC 61800-5-1 states that either the 
power supply must be automatically disconnected in case of discontinuity of 
the protective earthing conductor or a protective earthing conductor with a 
cross-section of at least 10 mm
2
 (Cu) or 16 mm
2
 (Al) must be used. Failure 
to comply may result in death or serious injury.
 ● For personal safety and reliability of the equipment, it is important to connect ground 
(PE) terminal to an effective electrical ground. Resistance value of the ground cable 
must be less than 10 Ω.
 ● Do not connect the grounding (PE) terminal of the drive to neutral conductor of the 
power system.
 ● Protective grounding conductor must be able to carry large short-term current that 
might arise if a fault occurs.
 ● Use proper grounding cable with yellow/green insulation for protective grounding 
conductor.
 ● Ground the shield.
 ● It is recommended that the drive be installed on a metal mounting surface.
 ● Install lter and drive on the same mounting surface and ensure ltering effect.